(!) Since support from Microsoft will end on January 14th, 2020, Windows 7 will be excluded from the recommended environment from December 15th, 2019 on this site. Vì lý do Microsoft kết thúc hỗ trợ cho Windows 7 vào ngày 14/01/2020, Windows 7 sẽ là hệ điều hành không được khuyến khích sử dụng với trang web này từ ngày 15/12/2019.
Select part number to Order Now/ Add to Cart
[Features]
· Improved ease of use and convenience; a new standard in timer switches.
· In addition to the weekly 2ch type, 4ch type a year-long series has also been added.
· Operability greatly improved by the use of an independent day-of-the-week key.
· Output of bank holidays and non-weekdays OFF enabled by a simple holiday setting function.
· It can also be set when the power supply is OFF.
· A simple test mode for program checks.
· UL/CSA, acquired the cheaper power law standard, suited to the EMC standard.
Series H5S-□A□ / -□B□ dimensional outline drawing
Series H5S-□A□ / -□B□ panel cut dimensions
Series H5S-□FA□ / -□FB□ dimensional outline drawing
Series H5S-□FA□ / -□FB□ mounting hole processing dimensions (when surface mounting)
When mounting a large terminal cover (sold separately)
When DIN rail is mounted
Type | Weekly 2ch (Series H5S-W□2) | Yearly 2ch (Series H5S-Y□2) | Yearly 4ch (Series H5S-Y□4) | ||
---|---|---|---|---|---|
Power Supply Voltage | · 100 to 240 V AC, 50/60 Hz Common *1 · 24 V DC | ||||
Allowable Voltage Variation Range | 85 to 110% of power supply voltage (AC power supply type) 85 to 120% of power supply voltage (DC power supply type) | ||||
Power Consumption | Approx. 2.9 VA (At 264 V AC, 60 Hz) Approx. 0.8 W (At 28.8 V DC) | Approx. 3.2 VA (At 264 V AC, 60 Hz) Approx. 0.9 W (At 28.8 V DC) | Approx. 3.5 VA (At 264 V AC, 60 Hz) Approx. 1.0 W (At 28.8 V DC) | ||
Control Output | Number Of Circuits | 2 Circuits Independent (2a) | 4 Circuits Independent (4a) | ||
Circuit | Power supply circuit and other (no-voltage) circuit | ||||
Capacity | Resistive load (cosø = 1) | 250 V AC, 15 A *2 | 250 V AC, 3 A | ||
Inductive Load | 250 V AC, 10 A (cosø = 0.7) | 250 V AC, 2 A (cosø = 0.4) | |||
Ambient Operating Temperature | -10 to +55°C (No Freezing Or Condensation) | ||||
Ambient Operating Humidity | 25 to 85% | ||||
Storage Temperature | -25 to +65°C (No Freezing Or Condensation) | ||||
Case Exterior | Light Gray (Munsell 5Y7/1) |
*1. Do not use the inverter output as a power supply. For details, refer to the "Safety Precautions" in the catalog.
* 2 The capacity is 15 A per circuit, but derating of the total current for two circuits is required.
Type | Weekly 2ch (Series H5S-W□2) | Yearly 2ch (Series H5S-Y□2) | Yearly 4ch (Series H5S-Y□4) | |
---|---|---|---|---|
Variations In Operating Time | (±0.01% ±0.05 s) or less*1 ±0.01% is the value for the set time interval. | |||
Set Error | ||||
Voltage Effect | ||||
Temperature Effect | ||||
Cyclic Error | ±15 s/month (25°C) | ±15 s/month (−10 to +45°C), ±20 s/month (+45 to +55°C) | ||
Compensation Time For Power Outage | Continuous 5 years or more (25°C) *2 | |||
Insulation Resistance | 100 MΩ or more (between conductive part terminal and exposed non-charging metal part, between operation power supply circuit and control output, between control outputs, between discontinuous contacts) | |||
Withstand Voltage | 2,950 V AC, 50/60 Hz, 1 min (between conductive part terminal and exposed non-charging metal part) 2,000 V AC, 50/60 Hz, 1 min (between operation power supply circuit and control output, between control outputs) 1,000 V AC, 50/60 Hz, 1 min (between discontinuous contacts) | |||
Noise Resistance | ±1,500 V: between power supply terminals (AC power supply type) ±500 V: between power supply terminals (DC power supply type) Square-wave noise by noise simulator (pulse width 100 ns/1 μs, rise 1 ns) | |||
Vibration | Endurance | 10 to 55 Hz, half amplitude 0.375mm, 3 directions, 2 h each | ||
Malfunction | 10 to 55 Hz, half amplitude 0.25mm, 3 directions, 10 min each | |||
Shock | Endurance | 300 m/s2, 3 axes, 6 directions, 3 times each | ||
Malfunction | 100 m/s2, 3 axes, 6 directions, 3 times each | |||
Life | Mechanical | 100,000 operations or more | ||
Electrical | 50,000 operations or more (resistive load, 250 V AC, 15 A) 50,000 operations or more (resistive load, 30 V DC, 10 A) 50,000 operations or more (inductive load, 250 V AC, 10 A, cosø = 0.7) 50,000 operations or more (motor load, 250 V AC, 1 HP) 50,000 operations or more (lamp load, 100 V AC, 100 W) 10,000 operations or more (lamp load, 100 V AC, 300 W) | 50,000 operations or more (resistive load, 250 V AC, 3 A) 50,000 operations or more (resistive load, 30 V DC, 3 A) | ||
Mass | Approx. 200 g |
*1. Total error including variations in operating time, set errors, and the effects of voltage and temperature are (±0.01% ±0.05 s) or less.
* 2. The compensation time for power outage is the calculated value when the ambient temperature is 25°C during a power outage (storage). Clock function and setting program are backed up by the built-in lithium battery, so the information will be erased when the battery dies. Please understand that the registered contents will be erased when the lithium battery is replaced (circuit board replacement).
Safety Standards | cURus: UL508/CSAC22.2 No. 14 EN60730-2-7: Pollution Degree 2, Overvoltage Category II VDE0106/part100 Product Safety of Electrical Appliance and Material |
---|---|
EMC | (EMI): EN60730-2-7 Radiation interference field strength: EN60730-2-7 (CISPR22 class B) Noise terminal voltage (continuous): EN60730-2-7 (CISPR22 class B) Noise terminal voltage (non-continuous): EN60730-2-7 (CISPR14-1) Harmonic current: EN60730-2-7 (IEC61000-3-2 class A) Voltage variation/flicker: EN60730-2-7 (IEC61000-3-3) (EMS): EN60730-2-7 Electrostatic discharge immunity: EN60730-2-7 (IEC61000-4-2): 6 kV direct, 8 kV atmospheric Field strength immunity: EN60730-2-7 (IEC61000-4-3): 10 V/mAM modulation (80 to 1,000, 1,400 to 2,000 MHz), 10 V/m pulse modulation (900 MHz) Conductive noise immunity: EN60730-2-7 (IEC61000-4-6): 10 V (0.15 to 80 MHz) Burst noise immunity: EN60730-2-7 (IEC61000-4-4): 2 kV (power supply line), 1 kV (control line) Surge immunity: EN60730-2-7 (IEC61000-4-5): 1 kV between lines (power supply line, output line), 2 kV between grounds (power supply line, output line), 0.5 kV between lines (input line), 1 kV between grounds (input line) Voltage dip / interruption immunity: EN60730-2-7 (IEC61000-4-11): 0.5 s cycles, 100% (rated voltage) |
Part Number |
---|
H5S-WA2 |
H5S-WB2 |
H5S-WFA2 |
H5S-WFB2 |
H5S-YA2-X |
H5S-YA4-X |
H5S-YFA2-X |
Part Number | Price | Minimum Order Qty. | Volume Discount | Days to ShipSố ngày giao hàng | RoHS | Mounting Method | Time specifications (s) | Power Supply Voltage | Dimension vertical (mm) | Dimension depth (mm) | Rated power supply voltage (V) | Contact Configuration |
---|---|---|---|---|---|---|---|---|---|---|---|---|
3,950,000 VND | 1 Piece(s) | 11 Day(s) | - | Panel | Control cycle: 7-Day (1-min units) | AC-dedicated | 72 | 62.7 | AC 100–240 | 2a | ||
4,824,000 VND | 1 Piece(s) | 7 Day(s) or more | - | Panel | Control cycle: 7-Day (1-min units) | AC-dedicated | 72 | 62.7 | AC 100–240 | 2a | ||
3,890,000 VND 3,189,800 VND | 1 Piece(s) | Same day | - | [Other] Surface mounting | Control cycle: 7-Day (1-min units) | AC-dedicated | 96 | 71 | AC 100–240 | 2a | ||
5,001,781 VND | 1 Piece(s) | 11 Day(s) | - | [Other] Surface mounting | Control cycle: 7-Day (1-min units) | AC-dedicated | 96 | 71 | AC 100–240 | 2a | ||
5,356,125 VND | 1 Piece(s) | 11 Day(s) | - | Panel | Control cycle: year (1-min units) | AC-dedicated | 72 | 62.7 | AC 100–240 | 2a | ||
10,859,298 VND | 1 Piece(s) | 7 Day(s) or more | 10 | Panel | Control cycle: year (1-min units) | AC-dedicated | 72 | 62.7 | AC 100–240 | 4a | ||
5,356,125 VND | 1 Piece(s) | 7 Day(s) or more | - | [Other] Surface mounting | Control cycle: year (1-min units) | AC-dedicated | 96 | 71 | AC 100–240 | 2a |
Loading...Tải…
Type | Time switch | Display method | Liquid Crystal | Output Method | Relay |
---|---|---|---|---|---|
Representative Standard | UL / CSA | Dimension width(mm) | 72 |
How can we improve?
How can we improve?
While we are not able to respond directly to comments submitted in this form, the information will be reviewed for future improvement.
Customer Privacy Policy
Thank you for your cooperation.
While we are not able to respond directly to comments submitted in this form, the information will be reviewed for future improvement.
Please use the inquiry form.
Customer Privacy Policy